Power cables with plastic insulation and sheath

АВВГ, АВВГз, АВВГнг(А), АВВГзнг(А), АВВГнг(А)-П, АВВГзнг(А)-П, АВВГнг(А)-LS

DESIGNATION

 

Power cables with aluminum conductors in plastic insulation and sheath are designed for power transmission and distribution in fixed units and fixed installation of power lines with rated alternating voltage of 660 V or 1000 V and 50 Hz frequency.

Cable models and their definitions shall correspond to the details given in the table below:

Model

Definition

АВВГ

Power cable with aluminum conductors, in PVC compound insulation, with PVC compound sheath

АВВГз

Power cable with aluminum conductors, in PVC compound insulation, with PVC compound sheath, with "з" index (filling of space between conductors)

АВВГнг(А)

Power cable with aluminum conductors, in PVC compound insulation, with fire-resistant PVC compound sheath

АВВГзнг(А) 

Power cable with aluminum conductors, in PVC compound insulation, with fire-resistant PVC compound sheath, with "з" index (filling of space between conductors)

АВВГнг(А)-П

Power cable with aluminum conductors, in PVC compound insulation, with fire-resistant PVC compound sheath, with "П" index (flat)

АВВГзнг(А)-П

Power cable with aluminum conductors, in PVC compound insulation, with fire-resistant PVC compound sheath, with "П" index (flat), with "з" index (filling of space between conductors)

АВВГнг(А)-LS 

Power cable with aluminum conductors, in flame-retardant PVC compound insulation and sheath with low gas and fume emission

 

ARRANGEMENT

CONDUCTOR:  aluminum, solid or stranded, round

INSULATION: PVC compound; for cables with "нг(А)" index - fire-resistant PVC compound; for cables with "нг(А)-LS" index - flame-retardant PVC compound with low gas and fume emission. Insulated conductors have distinctive color. Neutral conductor - blue colored; ground conductor - green-and-yellow colored.

STRAND: insulated conductors are stranded. Parallel lay in two-core cables is allowed.

FILLING: for cables with PVC compound insulation - PVC compound. In cables of АВВГз model PVC compound filling shall be laid together with sheath provided that they are easily separated without damage.

SHEATH:  PVC compound; for cables with "нг(А)" index - fire-resistant PVC compound; for cables with "нг(А)-LS" index - flame-retardant PVC compound with low gas and fume emission.

NUMBER OF CONDUCTORS:  1, 2, 3, 4, 5.

CONDUCTOR AREA, mm²:  1.5; 2.5; 4.0; 6.0; 10.0; 16.0; 25.0; 35.0; 50.0.

TECHNICAL SPECIFICATIONS

Operating temperature range:

- for АВВГ, АВВГз cables - from -50°С to +50°С;

- for АВВГнг(А), АВВГзнг(А), АВВГнг(А)-П, АВВГзнг(А)-П cables - from -30°С to +50°С;

- for АВВГнг(А)-LS cables - from -40°С to +50°С;

Cables shall be resistant to the effect of relative atmospheric humidity up to 98% at ambient temperature up to +35°C.

Cables do not spread combustion when laid as harness.

Factory cable length: for up to 16.0 mm² conductor area - 450 m; for from 25.0 to 50.0 mm² conductor area - 300 m.

Supplies of cables with not less than 50 m length at a quantity of not more than 15% of the batch are allowed.

Average operational life of cables - 30 years.

Regulations: GOST 16442-80, Technical Specifications of The Republic of Belarus 500017371.030-2004, Technical Specifications BY 500017371.045-2009.